Temperature sensor/

Rosemount RTD/thermocouples

■The temperature measurement range of RTD is as follows: -196 to 600°C (-321 to 1112°F);

The temperature measurement range of thermocouples is: -196 up to 1200°C (-321 to 2192°F)

■ Industry-standard sensor type:PT100 RTD;Type J、 Type K and Type T thermocouples

■Mounting method of spring pressure and compact spring pressure sensor

■ Hazardous Location Product Certification and Certificates

■Calibration service enables you to achieve better sensor performance

■ A calibration certificate is included with the sensor

Consultation telephone:19991827169

  • Product Details

Insulation resistance

When measured at 500VDC and room temperature,The minimum insulation resistance is 1000 M 。

Insulation resistance at high temperatures

When in 500 VDC and when measured at maximum temperature,The minimum insulation resistance is 400 M 。

Response time

When in accordance with the IEC 60751:2008 when tested in running water,attain 50% Sensor response is required at most 10.8 second

stability

According to IEC 60751:2008 The method specified in,Passed at the maximum specified temperature 1,000 The maximum freezing resistance drift measured after hours was ±0.15°C (0.059 )

Effect of temperature cycling

According to IEC 60751:2008 The method specified in,Passed at the maximum specified temperature 10 The maximum measured freezing point resistance drift after cycles is ±0.15°C (0.059 )

Lag

According to IEC 60751:2008 The method specified in,The maximum freezing resistance drift measured over the maximum specified temperature range is ±0.50°C (0.185 )

Self-heating

According to IEC 60751:2008 The method specified in,The measured average is: 0.32 ℃/mW。


Insulation resistance

When measured at 500VDC and room temperature,The minimum insulation resistance is 1000 M 。

Response time

Grounded thermocouples

When in accordance with the IEC 61515:2016 when tested in running water,attain 50% Sensor response is required at most 2.2 second。

Ungrounded thermocouples

When in accordance with the IEC 61515:2016 when tested in running water,attain 50% Sensor response is required at most 3.2 second。

Process immersion

Grounded thermocouples

Minimum immersion depth = 5 mm,According to IEC 61515:2016 Measured in water at 100°C。

Ungrounded thermocouples

Minimum immersion depth = 10 mm,According to IEC 61515:2016 Measured in water at 100°C。

continuity

Verify the electrical continuity of each conductor。For grounding point thermocouples,Verify the electrical continuity of each pair of conductors and sheaths。

Lead

Lead -24 AWG leads;FEP insulation;According to IEC 60584 or ASTM E230 for color coding。